EWD Steam/Hot Water: Technical Data

| Model EWD |
Nozzle Length |
Max. Vol (FPM) |
Max. Vol (CFM) |
Motors (HP) |
Steam (MBTU/HR) |
Steam Temp Rise (F) |
Hot Water (MBTU/HR) |
H.W. Temp Rise (F) |
Net Wt. (lb) |
| 1-96 |
96 |
6,000 |
25,000 |
20 |
968 |
35 |
608 |
23 |
1,000 |
| 1-108 |
108 |
6,000 |
28,000 |
20 |
1,089 |
35 |
684 |
23 |
1,050 |
| 1-120 |
120 |
6,000 |
29,300 |
25 |
1,120 |
35 |
760 |
23 |
1,125 |
| 1-144 |
144 |
6,000 |
36,000 |
30 |
1,452 |
35 |
912 |
23 |
1,350 |
| 1-168 |
168 |
6,000 |
42,000 |
30 |
1,694 |
35 |
1,064 |
23 |
1,550 |
| 2-192 |
192 |
6,000 |
48,000 |
20+20 |
1,936 |
35 |
1,216 |
23 |
1,825 |
| 2-216 |
216 |
6,000 |
54,000 |
20+25 |
2,178 |
35 |
1,368 |
23 |
2,100 |
| 2-240 |
240 |
6,000 |
60,000 |
25+25 |
2,420 |
35 |
1,520 |
23 |
2,300 |
| 2-264 |
264 |
6,000 |
66,000 |
25+30 |
2,662 |
35 |
1,672 |
23 |
2,500 |
| 2-288 |
288 |
6,000 |
72,000 |
30+30 |
2,904 |
35 |
1,824 |
23 |
2,800 |
Standard Voltages: 200/208/230/240/400/416/460/480/575/3 phase 60hz.
50hz AVAILABLE ON REQUEST Sound Level Measured 10' from unit in free field: 85dbA. Rating
based on 70 degrees F entering air, 5 p.s.i. steam or 180 degrees F hot water. |
|
Miniveil Air Systems
340 Ward St. Port Hope, ON
CANADA L1A 4A6
Telephone: 1-905-885-4015
Fax: 1-905-885-6478
Email: info@miniveil.com
|
|