CFF Steam/Hot Water: Technical Data
| Model CFF |
Nozzle Length |
Max. Vol (FPM) |
Max. Vol (CFM) |
Motor (s) hp |
Steam (MBTU/HR) |
Steam Temp Rise (F) |
Hot Water (MBTU/HR) |
H.W. Temp Rise (F) |
Net Wt. (lb) |
| 1-60 |
60 |
3,000 |
4,500 |
1.5 |
259 |
52 |
146/td> |
30 |
510 |
| 1-72 |
72 |
3,000 |
5,400 |
1.5 |
315 |
52 |
175 |
30 |
550 |
| 1-96 |
96 |
3,000 |
7,200 |
3 |
415 |
52 |
233 |
30 |
720 |
| 1-120 |
120 |
3,000 |
8,800 |
3 |
500 |
52 |
281 |
30 |
935 |
| 1-144 |
144 |
3,000 |
10,800 |
5 |
621 |
52 |
297 |
30 |
1,155 |
| 2-168 |
168 |
3,000 |
12,500 |
5 |
724 |
52 |
346 |
30 |
1,350 |
Standard Voltages: 200/208/230/240/400/416/460/480/575/3 phase 60hz
Sound Level Measured 10' from unit in free field: CFF, 52 dbA
Steam Rating Based on 70 degrees F entering air, 5 p.s.i. steam
Hot Water rating based on 70 degrees F. entering air, 180 degrees F entering water temp |
|
Miniveil Air Systems
340 Ward St. Port Hope, ON
CANADA L1A 4A6
Telephone: 1-905-885-4015
Fax: 1-905-885-6478
Email: info@miniveil.com
|
|