CFA Steam/Hot Water: Technical Data

| Model CFA |
Nozzle Length |
Max. Vol. (FPM) |
Max. Vol. (CFM) |
Motors (HP) |
Net Wt. (lb) |
Steam (MBTU/HR) |
Steam Temp Rise (F) |
Hot Water (MBTU/HR) |
H.W. Temp Rise (F) |
| 1-60 |
60 |
4,000 |
6,400 |
3 |
415 |
312 |
45 |
167 |
24 |
| 1-72 |
72 |
4,000 |
7,700 |
3 |
445 |
376 |
45 |
200 |
24 |
| 1-96 |
96 |
4,000 |
12,400 |
5 |
585 |
498 |
45 |
266 |
24 |
| 1-120 |
120 |
4,000 |
12,400 |
5 |
775 |
605 |
45 |
323 |
24 |
| 1-144 |
144 |
4,000 |
15,300 |
7.5 |
960 |
747 |
45 |
398 |
24 |
| 2-168 |
168 |
4,000 |
17,800 |
3+5 |
1,120 |
871 |
45 |
464 |
24 |
| 2-192 |
192 |
4,000 |
20,400 |
5+5 |
1,280 |
996 |
45 |
531 |
24 |
| 2-216 |
216 |
4,000 |
22,320 |
5+5 |
1,530 |
1,089 |
45 |
581 |
24 |
| 2-240 |
240 |
4,000 |
24,800 |
5+5 |
1,700 |
1,210 |
45 |
646 |
24 |
| 2-264 |
264 |
4,000 |
27,290 |
5+7.5 |
1,870 |
1,331 |
45 |
711 |
24 |
| 2-288 |
288 |
4,000 |
28,760 |
7.5+7.5 |
2,040 |
1,452 |
45 |
775 |
24 |
Standard Voltages: 200/208/230/240/400/416/460/480/575/3 phase 60hz. Sound
Level Measured 10' from unit in free field: CFA, 73dbA. Rating based on 70 degrees F
entering air, 5 p.s.i. steam or 180 degrees F hot water. |
|
Miniveil Air Systems
340 Ward St. Port Hope, ON
CANADA L1A 4A6
Telephone: 1-905-885-4015
Fax: 1-905-885-6478
Email: info@miniveil.com
|
|