AFA Steam/Hot Water: Technical Data

| Model AFA |
Nozzle Length |
Max. Volume (FPM) |
Max. Volume (CFM) |
Motors (HP) |
Steam (MBTU/HR) |
Steam Temp Rise (F) |
Hot Water (MBTU/HR) |
H.W. Temp Rise (F) |
Net Wt. (lb) |
| 1-36 |
36 |
3,000 |
1,875 |
1/2 |
81 |
40 |
61 |
30 |
178 |
| 2-48 |
48 |
3,000 |
2,500 |
2 x 1/2 |
109 |
40 |
81 |
30 |
208 |
| 2-60 |
60 |
3,000 |
3,120 |
2 x 1/2 |
135 |
40 |
102 |
30 |
229 |
| 2-72 |
72 |
3,000 |
3,750 |
2 x 1/2 |
163 |
40 |
122 |
30 |
261 |
| 2-84 |
84 |
3,000 |
4,380 |
2 x 1/2 |
190 |
40 |
143 |
30 |
291 |
| 3-96 |
96 |
3,000 |
5,000 |
3 x 1/2 |
217 |
40 |
163 |
30 |
313 |
| 3-108 |
108 |
3,000 |
5,625 |
3 x 1/2 |
244 |
40 |
183 |
30 |
333 |
| 4-120 |
120 |
3,000 |
6,240 |
4 x 1/2 |
271 |
40 |
203 |
30 |
354 |
| 4-144 |
144 |
3,000 |
7,500 |
4 x 1/2 |
326 |
40 |
244 |
30 |
395 |
Standard Voltages: 115/208/230/ 1 phase 60 hz.
Sound Level Measured 10' from unit in free field: AFA, 54 dbA low speed: 59 dbA high
speed.
Steam Rating Based on 70 degrees F entering air, 5 p.s.i. steam with a
temp rise of 40 degrees F
Hot Water rating based on 70 degrees F. entering air, 200 degrees F entering water temp
with a temperature rise of 30 degrees F. |
|
Miniveil Air Systems
340 Ward St. Port Hope, ON
CANADA L1A 4A6
Telephone: 1-905-885-4015
Fax: 1-905-885-6478
Email: info@miniveil.com
|
|